FY series current, voltage transformer load box supply various real load when test current or voltage transformer, it is the ideal auxiliary product for transformer detectors. It is strictly designed according JJG313-94 ,JJG314-94 , it is with advantages of large output capacity, great variety of load, light weight, beautiful outlook, strong stability, etc.
Alternative Name
transformer load box ,CT load box, PT load box
Light weight, beautiful outlook, high capacity and strong stability,
1. FY96-H current transformer load box
Main technique parameters
condition of circumstance
temperature: 15-25℃ humidity: <80%(25℃)
humidity: < 1500m frequency:50Hz
rated capacity: COS0.8: 2.5VA-60VA; COS1.0: 2.5VA-20VA;
measurement range:
current: 1%-120%
secondary current:5A
power factor:0.8, 1.0
accuracy: ±3%±0.0025VA
test voltage:2KV
dimension: 250 mm×350 mm×175 mm
weight:8kg
2. FY96-A current transformer load box
Main technique parameters
condition of circumstance
temperature: 15-25℃ humidity: <80%(25℃)
humidity: < 1500m frequency:50Hz
rated capacity: COS0.8: 2.5VA-60VA; COS1.0: 2.5VA-20VA;
measurement range:
current: 5%-120%
secondary current:1A
power factor:0.8, 1.0
accuracy: ±3%±0.0025VA
test voltage:2KV
dimension: 250mm×350mm×175mm
weight:8kg
3. FY95-H voltage transformer load box
Main technique parameters
condition of circumstance
temperature: 15-25℃ humidity: <80%(25℃)
humidity: < 1500m frequency:50Hz
rated capacity: 1.25VA-158.75VA
measurement range:20%-120%
secondary voltage:110/ V
power factor:0.8, 1.0
accuracy: ±3%±0.05VA
test voltage:2KV
dimension: 250mm×350mm×175mm
weight:8kg
4. FY95-A voltage transformer load box
Main technique parameters
condition of circumstance
temperature: 15-25℃ humidity: <80%(25℃)
humidity: < 1500m frequency:50Hz
rated capacity: 1.25VA-158.75VA
measurement range:20%-120%
secondary voltage:110/ V
power factor:0.8, 1.0
accuracy: ±3%±0.05VA
test voltage:2KV
dimension: 250mm×350mm×175mm
weight:8kg
5. FY98-H current voltage transformer load box
Main technique parameters
condition of circumstance
temperature: 15-25℃ humidity: <80%(25℃)
humidity: < 1500m frequency:50Hz
rated capacity:
current :COS0.8: 2.5VA-60VA; COS1.0: 2.5VA-5VA;
voltage: 1.25VA-158.75VA
measurement range:
current: 1%-120% voltage: 20%-120%
secondary current:1A
secondary voltage:110/ V
power factor:0.8, 1.0
accuracy:
current: ±3%±0.0025VA voltage: ±3% ±0.05VA
test voltage:2KV
dimension: 340mm×350mm×175mm
weight:15kg
6. FY98-A current voltage transformer load box
Main technique parameters
condition of circumstance
temperature: 15-25℃ humidity: <80%(25℃)
humidity: < 1500m frequency:50Hz
rated capacity:
current :COS0.8: 2.5VA-60VA; COS1.0: 2.5VA-5VA;
voltage: 1.25VA-158.75VA
measurement range:
current: 5%-120% voltage: 20%-120%
secondary current:1A
secondary voltage:110/ V
power factor:0.8, 1.0
accuracy:
current: ±3%±0.0025VA voltage: ±3% ±0.05VA
test voltage:2KV
dimension: 340mm×350mm×175mm