Products
Transformer Tester
HV Testing Equipment
Series Resonant Equipment
Secondary Circuit Tester
Cable/Lightening Arrester Tester
Earth/Insulation Series
Electrical Measurement & Transformer
Other Electrical Tester
test1
test2
test3
test4
Recommended Products
Contact Us
  • ADD:China Wuhan East Lake hi tech Development Zone (Optics Valley of China)
    TEL:+86 400-6884446
    FAX:+86 400-6884446
    E-mail:whguozi@163.com

GOZ-2572 Earth Resistance Tester

GOZ-2572 Earth Resistance Tester
  • Earth Resistance Tester
Product Description
     GOZ-2572 Earth Resistance Tester was designed according IEC, ISO, BS, VL, JIS, etc standards. Earth resistance is an important index to measure the safety performance for all kinds of equipments. It tests the earth resistance under current (25A or 10A), avoid to hurt people if the insulating property reduced (or broken).
Alternative Name
    Digital ground resistance tester, ground resistance tester
Product illustrations
 
Product Features
 1. GOZ_2572 applies to the resistance between shell and its power earthing of all kinds of generator, electrical equipment, device. 
2. This device with two gears measuring current (R<200 mΩ( AC 25A) or 200 mΩ<R<600 mΩ (AC 10A)), measuring time:1~99 S.
3.With sound & light alarm if the measured value exceed the setting value.
4. High precision, easy to operate, small in volume.
5. Digital display, directly display, reliable, with open circuit alarm function.
Product parameters
  1. Service conditions: 

   (1) temperature:0~40 
   (2) relative humidity
80%
   (3) power supply:AC220V
±10%,50Hz
   (4) surroundings without strong electromagnetic interference, without a lot of dust and corrosive gas, with good ventilation 
2. Product features: 
   (1) Automatic compensate wire resistance and clamp contact resistance. 
   (2) Auto shift the measurement range. 
   (3) With over-current and undercurrent indication and protection functions. 
   (4) Remember the measurement conditions. 
   (5) With sound & light alarm. 
   (6) Single or continuous test, applies to production line. 
   (7) Front panel typed software calibration. 
   (8) Computer communication interface optionally. 
   (9) Control interface optionally. 
3. Technical parameters see table 1.

Measurement range(mΩ)

Measured current(A)

25.0~30.0

20.0~150.0

 

10.0~25.0

20.0~199.9

 

4.0~10.0

20.0~500

Intrinsic error

±(3%r+3d)

Measured current

A

40.0~30.0

Intrinsic error

±(3%r+3d)

Measured voltage(AC)(V)

6

Alarm resistance 
m
Ω

Resolution

0.1

1.0~199.9

1

200~500

Measured time  (s)

0~99±5

Note: 0 is continuous testing status, it means measured time infinity.

Dimension

380mm x 320mm x 145mm

Weight

9 kg

Note 1: r-reading ;  d-number of characters.
Note 2: temperature  23±5, relative humidity
80%。

 

Related Products:
Related Articles: