Applies to test the DC parameters of Oxide Zinc arrester (voltage dependent resistor), cermet second, third electrode discharge tube, vacuum lightning tube and others over-voltage protection components.
Alternative Name
Lightening protection components tester
1. Applies to test the DC parameters of Oxide Zinc arrester (voltage dependent resistor), cermet second, third electrode discharge tube, vacuum lightning tube and others over voltage protection components. It also can be considered as stable power source and constant current power supply.
2. With HV short circuit protection, over current protection, high voltage preset, range adjustment functions, HV self discharge time less than 0.5 second.
3. With self calibration function.
4. LCD display, high precision, strong reliability.
5. Pre-set the measurement range when testing, there will be sound alarm if exceed the measurement range.
6. Choose continuous measurement can make continuous test for mass measured equipments.
7. Panel function is simple, easy to operate.
8. Light in weight , easy to carry.
1. Voltage dependent resistor measurement
|
Technical Specifications
|
Measurement range
|
Maximum error
|
Test Conditions
|
|
Voltage (U 1mA)
|
( 0 ~ 1700 )V
|
≤±2%±1d
|
1mA±5μA
|
|
Leakage current ( I 0.75U 1mA)
|
(0.1 ~ 199.9 ) μA
|
±(2 μA +1d)
|
0.75 U1mA
≤±2%±1d
|
2. Discharge tube measurement
|
Technical Specifications
|
Measurement range
|
Maximum error
|
Test Conditions
|
|
DC breakdown voltage( V sdc )
|
(20 ~ 1700)V
|
≤±2%±1d
|
Rate of voltage rising
100V/S±10%
|
3. Voltage dependent resistor measurement
Insulating resistance: 6MΩ(500V)
Voltage withstand: AC 1.5kV 50HZ 1min
Service conditions:
Temperature : 0~+40℃ humidity≤85%RH
Storage conditions:
Temperature:-10℃~+50℃ humidity≤90%RH
Power supply: AC220V 50Hz
DC 12V 0.5A (core +pole)
Power consumption: 8W
Dimension: 208mmx190mmx78mm
sWeight: ≤1kg