GOZ-SMG2000B Clamp Phase Meter

GOZ-SMG2000B Clamp Phase Meter
Product Description
     SMG2000B Double Clamp Digital Phase Meter is special designed for voltage, current and phase tests, it is in high-precision, low price, portable hand-held, dual-channel input measuring. It's easy to measure the phase between U-U, I-I and U-I, identify the inductive circuit ,capacitive circuit and the phase sequence of three-phase voltage, detect the wiring group of transformer, test the secondary circuit and bus differential protection system, display the phase relationship among the CT groups of a differential protection system, and check if the wire of electric meter was correctly connected. When testing customers do not need cut off the tested current which input by slip core current transformer. When measuring the phase between U1 and U2, the two input circuit loop are completely isolated, so the possible misconnection is absolutely avoided, which may result in short circuit and may even burn the meter. The monitor of the device is high-contrast LCD screen, and the character in which could be as high as 25mm, and can be freely rotated approximately 70 °, which helps to obtain the best visual effects.
    The shell of the device is made of engineering insulating material, together with a rubber–made anti-vibration protection kits for safety and reliability.
 
Alternative Name
     Phase meter, clamp phase meter, digital clamp phase meter
Product illustrations
 
Product Features
 1. Withstand Voltage
Parts between voltage input terminal and meter shell, parts between the iron core of the clamp-current transformer and secondary windings can stand 1000V/50Hz. Parts between the two voltage input terminals can stand Sinusoidal AC Voltage 500V/50Hz for 1min when testing.
2. Insulation Resistance
Between meter circuit and meter shell, between the two voltage input terminals:≥10MΩ
Product parameters
 Intrinsic Error

1. Reference Operating Conditions
(1) Temperature(23
±5)
(2) Moisture(45
75)% RH
(3) Wave forms of measured signal, sine wave
、β=0.02
(4) Frequency of measured signal(50
±0.2)Hz
(5) Position of Measured current carrying conductor in the nipper jaw, Optional position
(6) Amplitude range of measured signal when measuring phase, 
100
220V0.5A1.5A
(7) External reference frequency electromagnetic interference, Should be avoided
2. Limits of Intrinsic Error
(1) AC Voltage(see Table 1) 

Table 1  Error of AC Voltage

Measure range

Resolution

Limits of intrinsic error

20V

0.01V

±(1.2%RD+2)

200V

0.1V

±(1.0%RD+2)

500V

1V

±(1.2%RD+2)

      Input Impedance:All the measure range is 2MΩ
(2) Alternating current(see Table 2)

Table 2   Error of alternating current

Measure range

Resolution

Limits of intrinsic error

200mA

0.1mA

±(1.0%RD+2)

2A

1mA

10A

10mA

(3) Phase
U-U
U-II-I(see Table 3)

Table 3   Error of Power-frequency Phase

Range

Resolution

Limits of intrinsic error

0360°

1°

±3°


     Impedance of input voltage loop when measuring phase of U1-U2:40K
Ω
Operating error
1. Rated Operating Conditions
(1) Temperature (0
40)
(2) Moisture (20
80)% RH
(3) Wave forms of measured signal, sine wave
、β=0.05
(4) Frequency of measured signal,(50
±0.5)Hz
(5) Position of Measured current carrying conductor in the nipper jaw, Optional position.
(6) Amplitude range of measured signal when measuring phase, 
    Phase U1-U2, 30V
500V
    Phase I1-I2, 10mA
10.00A
    Phase U1-I2 or I1-U2, 10V500V10mA10.00A
(7) External reference frequency electromagnetic interference, should be avoided
2. Limits of Rated Operating Error
   Under the conditions described in 1, the limits of the rated operating error will not exceed twice of the limits of intrinsic error.
Other Technical Features
1. Display, three and half
2. Sampling Rate, 3 times per second
3. Power Supply, Single 9V laminated cell
current of power is less than 5mA
4. Dimension
   Meter shell, 192x95x55mm
   Nipper shell, 140
×42×20mm
   Nipper jaw, Φ7×9mm
5. Weight
   Meter body, 280g
   Measuring pliers, 2
×200g
6. Storage Conditions
   Temperature,
1050